Data Center Cooling Fans: Selection Guide for CRAC, CRAH, Fan Walls and Dry Coolers

Technical guide · SINDFAN engineering · updated October 2026

A data centre cooling fan is not one product. It is a family of duties — CRAH coil airflow, EC fan walls, condenser and dry-cooler exhaust, hot-aisle extract, and liquid-cooling dry coolers — and each one wants a different impeller. This guide sets out which fan goes where, how to size it from airflow and static pressure, why part-load efficiency decides the energy bill, and what to put in a specification so the fans you buy still hold up when the IT load changes.

Which fan goes where

DutyTypical fanStatic pressureWhat decides the choice
CRAH / CRAC coil airflowBackward-curved centrifugal plug fan, or EC fan wall300 – 800 PaPart-load efficiency, stable airflow against a loading coil and filter bank
EC fan wall (in-row and per-rack)EC plug fans in an array, 6 – 12 per unit200 – 600 PaRedundancy (N+1), individual fan speed control, shallow depth
Condenser / dry coolerAxial, 630 – 1250 mm80 – 200 PaLowest kW per m³/s, fan count, acoustic limit at the boundary
Hot-aisle extractAxial or mixed-flow50 – 150 PaRedundancy, easy replacement, low noise into the hall
Liquid-cooling dry cooler (CDU)Large axial, up to 1600 mm60 – 150 PaTurndown range, wind tolerance, low ambient starting
Make-up and pressurisationSmall axial30 – 100 PaFilter loading, controllability

Axial or centrifugal: the deciding number is static pressure

An axial fan moves a lot of air at low pressure. A centrifugal holds its flow as the pressure climbs. The crossover sits around 250 – 400 Pa. Below it, an axial fan almost always uses fewer watts per cubic metre. Above it, an axial fan starts to stall and the centrifugal wins — which is why CRAH units with dense coil faces use plug fans rather than propellers.

Two practical checks before you choose:

Why EC fans change the calculation

An EC (electronically commutated) motor carries its own speed control, so the fan follows the load instead of running at fixed speed and dumping energy through a damper or inlet guide vane. In most cooling systems resistance falls as airflow falls, so shaft power drops roughly with the cube of speed. Two things follow:

The trade-off is honest: the EC motor and its electronics cost more than a belt-driven AC fan of the same duty, and the electronics have their own temperature limit, so the fan has to be applied where the airstream temperature is within the motor's rating — a hot-aisle extract at 40 – 45 °C is a different duty from a dry cooler at ambient.

How to size a cooling fan

Four numbers define the duty, and every fan supplier should be asked for all four:

  1. Volumetric flow in m³/s or m³/h (or cfm) — the air the coil or the room actually needs, not the fan's free-air rating.
  2. Total pressure in Pa, at that flow — the resistance of coil, filter, duct, louvre, silencer and discharge, added up at the dirty-filter condition.
  3. Air density at the fan inlet — altitude and temperature both change it, and power follows density directly. A fan selected at sea level will be short of flow at 2000 m unless the density is corrected.
  4. Sound limit in dB(A) at the relevant distance or at the boundary — this often decides the tip speed, which then decides the fan size.

From these, the required shaft power follows from the air power divided by efficiency: P = Q × Pt / (1000 × η) with Q in m³/s, Pt in Pa and P in kW. Note that total pressure is the comparable figure, not static pressure alone: Pt = Ps + Pd, and Pd = ½ρv² at the fan outlet. Comparing a fan quoted on static pressure with one quoted on total pressure is a common way to buy the wrong machine.

What to put in the specification

Most data centre fan problems appear two years after handover, and most of them are specification gaps rather than manufacturing faults. Six lines worth writing into the enquiry:

One data center fan or a whole fan wall: where the airflow actually goes

Most selection errors start before the fan is chosen, in the way the air path is drawn. Each data center fan in a unit does not see the room average; it sees the pressure at its own inlet and outlet, and in a hot aisle containment arrangement the return path is what sets that pressure.

The order that avoids rework: fix the air path and the containment first, then the duty point per fan, then the redundancy state, and only then the fan itself. A data center fan chosen against the room average will be wrong in every one of the four cases above.

Common mistakes

Where SINDFAN fits

We manufacture axial fans and impellers from Ø250 to Ø3150 mm, and backward-curved centrifugal impellers, at our own works in Tianjin. For data centre duty that means:

Performance is stated to AMCA 210 / ISO 5801, impellers are balanced to ISO 1940 G6.3 or better, and test reports are supplied with each contract. We are a manufacturer, not a trading house: impellers are pressed, welded, heat treated and balanced in our own plant, which is why a non-standard diameter or blade angle is a normal order for us rather than a special project.

Ask us for the actual numbers

If you have a duty point — airflow, total pressure, density, sound limit and the number of fans — send it and we will come back with the fan size, the shaft power at 100 %, 75 % and 50 % flow, and the sound power. If you are replacing an existing impeller, send the diameter, the hub diameter, the blade count and a photo of the old impeller and we will match it.

Send your duty point